Désolé, cet article est seulement disponible en English et Deutsch. Pour le confort de l’utilisateur, le contenu est affiché ci-dessous dans la langue par défaut du site. Vous pouvez cliquer l’un des liens pour changer la langue du site en une autre langue disponible.
Service, Plant Performance Upgrades
district heat, electricity
Increasing Thermal Output Boosts Plant Performance by 22%
The Klemetsrud Line 3 WtE boiler was commissioned in 2011 with a nominal steam flow of 78.1 t/h. Since then Kanadevia Inova has increased the incineration capacity and energy output in several steps, each comprising a variety of different measures designed to increase the plant’s performance. After each step, the operation of the plant has been evaluated at the new nominal load, and a programme drawn up for the next step. This includes a thorough cost-benefit analysis. Now the boiler is operated at a steam flow of up to 110 t/h.
The first increase in steam flow – up 4% to 81.5 t/h – was achieved in 2015 by optimising the combustion control system.
- In 2016 the flow was increased to 90 t/h by installing additional condenser systems and direct heat extraction from the economisers, as well as improving the attemperators.
- In 2017 Kanadevia Inova installed an enhanced combustion control system to boost team flow for a third time, to 95 t/h.
- Performance was boosted once again in 2019, to 110 t/h, by installing Inconel cladded boiler walls and optimised cleaning systems preventing boiler foulage.
- Analysis and feasibility study
- Performance increase programmes and engineering
- Optimisation and installation works
- Adjustments to combustion control system
- Test runs